Example 10.24: requested quantities
10.24 Determine: β; Ẇcompr; Q̇evap (refrigeration capacity).
Using the page's approximations: β = 6.2, Ẇcompr = 434.9 W, and Q̇evap = 2699.1 W = 0.767 TR. The air-side load sets the refrigerant flow; enthalpy changes then determine compressor power and performance.
- At state 1, use the superheated R22 table at 4 bar and 10°C: h1 = 259.18 kJ/kg and s1 = 0.9795 kJ/(kg· K).
- The page approximates the isentropic discharge enthalpy at 9 bar as h2i = 280.68 kJ/kg. With compressor efficiency 0.7, h2r = 259.18 + (280.68-259.18)/0.7 = 289.89 kJ/kg approximately.
- State 3 is saturated liquid at 9 bar, so h3 = 68.59 kJ/kg. Adiabatic throttling gives h4 = h3.
- The page uses the outlet air density 1.209 kg/m3 and air mass flow 0.3829 kg/s. Its air-side calculation reports Q̇evap = 2699.1 W.
- Equate that load to ṁ(h1-h4), converting enthalpy from kJ/kg to J/kg: ṁ = 2699.1/[(259.18-68.59)103] ≈ 0.01416 kg/s.
- The page reports Ẇcompr = 0.01416(289.89-259.18)103 = 434.9 W and β = 2699.1/434.9 = 6.2.
- The page also reports Q̇cond = 3134.08 W. The later discussion distinguishes rounding and property-table limitations from the reported answer.
The page's approximate results are β = 6.2, compressor power 434.9 W, and refrigeration capacity 2699.1 W.